모듈러 데이터 센터에 적용된 직접식 외기냉방시스템의 다양한 제어기법에 관한 연구

주 저자함상우 *
공동 저자박준영 *, 정재원 **
소속모듈러 데이터 센터에 적용된 직접식 외기냉방시스템의 다양한 제어 기법에 관한 연구
AbstractThe main purpose of this research is to analyze various direct air-side economizer control strategies for a modular data center in respect to air-conditioning energy savings. Considering the fact that the reliability of electronics is the first priority in data centers, we set appropriate four air-side economizer control strategies and conducted annual energy simulation for the purpose of quantitative comparison. To the results, enthalpy-based air-side economizer showed best energy performance with 54.5% savings compared to reference system while there is limitation in physical configuration. On the other hand, ultrasonic humidifier assisted temperature based economizer represented good energy savings of 51% compared to reference with general physical configuration.
Keyword모듈러 데이터 센터, 외기냉방시스템, 외기냉방 제어
페이지pp. 243~244