제습증발냉각기반 전외기 공조시스템의 겨울철 운전에너지 성능 실증 분석

주 저자김민휘 *
공동 저자조수영 **, 정재원 ***
소속* 한양대 대학원 박사과정, ** 한양대 대학원 석사과정, *** 한양대 건축공학부 부교수, 공학박사 (교신저자)
AbstractThis study is to investigate the energy saving potential of desiccant and evaporative cooling-assisted 100% outdoor air system (LD-IDECOAS) in winter season. The pilot system was installed in office building and a conventional variable air volume (VAV) system was also installed to compare the energy performance of the proposed system. The temperature, humidity, and airflow sensors are installed on various measuring point to estimate the effectiveness of indirect evaporative cooler (IEC) and sensible heat exchanger(SHE). It was found that the effectiveness of IEC and SHE showed 85% and 69%, respectively. One can conclude that the LD-IDECOAS showed significant operating energy was saved via conventional VAV system.
Keyword제습시스템, 증발냉각시스템, 현열교환
페이지pp. 183~184
논문 파일
게재일시 -
DOI-
학회/저널명대한건축학회 춘계학술발표대회논문집 Vol.34, No.1
년도2014