Abstract | The main thrust of this research was to develop a simplified cooling capacity estimating correlation for a
top insulated metal ceiling radiant cooling panel (CRCP). By statistically analyzing the impact of various
panel design parameters on the panel cooling capacity, a linear regression equation was derived. A validated
analytical CRCP model was used to collect panel performance data for the various combinations of
design parameters. In this analysis, it was found that eight single design parameters and eleven two-factor
interactions significantly affect the panel cooling capacity. Consequently, a first order linear regression
equation, or the simplified CRCP model, was derived as a function of the major single parameters and twofactor
interactions. The proposed model returns the cooling capacity of a top insulated CRCP not only for
the natural convection condition but also for the mixed convection condition present in mechanically
ventilated spaces. The predicted panel cooling capacities for both aluminum and steel panels corresponded
well with manufacturer’s data and experimental results reported in the literature. |
Keyword | Radiant cooling; Ceiling radiant panel; Mixed convection; Natural convection; Radiant panel model |
페이지 | pp. 2055~2072 |
논문 파일 |
|
게재일시 |
-
|
DOI | - |
학회/저널명 | Applied Thermal Engineering Vol.24, No.14 |
년도 | 2004 |
추가 문구 | doi:10.1016/j.applthermaleng.2004.01.017 |