Abstract | Dedicated outdoor air systems (DOAS) integrated with
ceiling radiant cooling panels as a parallel sensible cooling
system are being considered as an alternative to conventional
variable air volume (VAV) systems for commercial buildings
because of their energy conservation, first and operating costs,
and indoor air quality advantages. A pilot DOAS/radiant panel
cooling system is being constructed on a university campus to
investigate its advantages over alternative cooling systems in
a real application. Prior to the actual operation of the pilot
system, the energy conservation potential of the DOAS/radiant
cooling panel system relative to a VAV system with air-side
economizer control was estimated. Hourly energy simulation
predicts that the annual electrical energy consumption of the
pilot DOAS/radiant panel cooling system is 42% less than that
of the conventional VAV system with air-side economizer. |