공기열원 히트펌프의 성능 향상을 위한 회전형 직접식 증발 냉각기의 실험 및 에너지 소비량 분석

주 저자박상환
공동 저자김범준, 정재원
소속한양대학교 건축공학과
AbstractThis study developed a novel rotational direct evaporative cooler and experimentally evaluated cooling performance. In the rotational direct evaporative cooler, the air is cooled by rotating media and the media is wetted in the sump without water spray. The developed system is tested in various air conditions to investigate the evaporative cooling performance of the proposed system. The results showed that evaporative cooling efficiency of the rotational direct evapo-rative cooler was 40–53% based on the water temperature. The comparison analysis was con-ducted for water and energy consumption with reference direct evaporative cooling system, and the proposed system uses less water and energy than the reference system. An energy consump-tion analysis was conducted for heat pump application, and 16.2% of energy savings was shown in the proposed system compared to a conventional heat pump air conditioning system.
KeywordDirect evaporative cooler, Air-source heat pump, Evaporative condenser, Coefficient of performance, Energy saving
페이지pp. 226~237
논문 파일 없음
게재일시 2024-06
DOI-
학회/저널명한국건축친환경설비학회논문집 Vol.18, No.3
년도2024
추가 문구https://doi.org/10.22696/jkiaebs.20240019