액체식 제습 시스템의 수조 농도 유지 방안에 따른 수용액 냉각 및 가열 부하 비교

주 저자이수진, 정재원
공동 저자-
소속-
AbstractThe purpose of this study was to compare the cooling and heating loads of liquid desiccant by maintaining the sump concentration in a liquid desiccant system. Case 1 is a liquid desiccant system with a dual sump based on solution exchange. Case 2 is a liquid desiccant system with membrane-based dual sump. Both cases are based on a dual sump, but the technologies used to maintain the concentration of solution in the sump differ. The concentration of the absorber and regenerator sumps in case 2 was similar to that of case 1. The results also indicated that case 2 required 71% lower cooling and heating load for solution than case 1 because the temperature of the absorber sump was lower and the temperature of the regenerator sump was higher. Therefore, case 2 saves energy for solution cooling and heating while maintaining dehumidification and solution regeneration.
KeywordDesiccant solution(제습 수용액), Cooling load(냉각 부하), Heating load(가열 부하) Dual sump(이중 수조)
페이지pp. 558~566
논문 파일
게재일시 -
DOI-
학회/저널명설비공학논문집 Vol.32, No.12
년도2020
추가 문구https://doi.org/10.6110/KJACR.2020.32.12.558