header-logo

유기랭킨사이클을 결합한 제습증발냉각 기반 공동주택 중앙 환기 시스템의 에너지 성능 분석

주 저자김범준
공동 저자동혜원, 정재원
소속-
AbstractA liquid desiccant-assisted dedicated outdoor air system (LDADOAS) with organic Rankine cycle (ORC) was proposed as a centralized ventilation system applicable to high-rise apartment buildings. The LDADOAS consists of a liquid desiccant dehumidifier and an indirect evaporative cooler for conditioning the minimum required outdoor air ventilation. The ORC considered in this research is a combined heat and power system to accommodate common electricity demand of the apartment building. The heat released from the ORC is used for regeneration of the desiccant solution in the proposed system. Energy performance of the proposed system was compared with existing dedicated outdoor air systems via detailed energy simulation. The result showed that the LDADOAS consumed 48% less primary energy consumption compared with conventional dedicated outdoor air system considered in this work because most of regeneration heat required for the proposed system was supplied by the waste heat recovered from the ORC.
Keyword-
페이지pp. 394~402
논문 파일 없음
게재일시 -
DOI-
학회/저널명한국건축친환경설비학회논문집 Vol.13, No.5
년도2019
추가 문구https://doi.org/10.22696/jkiaebs.20190034