header-logo

겨울철 오피스 환경의 쾌적성 향상을 위한 EHP 통합형 중공사막 가습기 적용성 분석

주 저자오정민
공동 저자이주현, 김세헌, 천성용, 정재원
소속-
AbstractSplit-type electric heat pump (EHP) systems, widely used in small and medium-sized offices, have limitations in maintaining the recommended indoor relative humidity (RH) range of 40-60% during winter heating period. This study proposes the integration of a hollow fiber membrane (HFM) humidifier into the indoor unit of an EHP system to provide hygienic and efficient humidification. The performance of this system was evaluated through a dynamic simulation, coupling an HFM numerical model with an indoor moisture dynamic model. Simulation results for the heating period showed that the proposed system maintained indoor humidity within the 40-60% comfort range, improving the thermal satisfaction ratio from 8% to 96% and enhancing the weekly average predicted mean vote (PMV) from below -0.5 to approximately -0.3. The findings confirm that the integrated HFM-EHP system can address winter dryness in offices and improve occupant thermal comfort.
KeywordMembrane humidifier, Split system, Indoor Air Quality
페이지-
논문 파일 없음
게재일시 2025-11
DOI-
학회/저널명2025 한국건축친환경설비학회 추계학술발표대회
년도2025
추가 문구-
등록 일시2025-12-24 15:53:23