액체식 제습 냉각시스템을 적용한 데이터센터의 기후지역별 에너지 소비 분석

주 저자박효림, 이수진, 정재원
공동 저자-
소속한양대학교 대학원 석사과정/ 한양대학교 대학원 박사과정/ 한양대학교 건축공학과 교수, 공학박사
AbstractIn this study, a liquid desiccant system was applied to the rear door cooling system to reduce the cooling energy of the data center. As the humidity of the outside air is lowered, the wet bulb temperature is also lowered. Energy used in the chiller could be reduced by lowering the cooling water outlet temperature of the cooling tower. The outdoor air used was used in the last three areas with high latitudes (Cheolwon, Chuncheon, and Seoul) and two areas with low latitudes (Daegu and Gwangju). As a result of simulation, the chiller saved energy up to 37.19%, and the PUE value could be reduced by 5%.
Keyword데이터센터, 폐열회수, 액체식제습, PUE