전열교환 환기장치의 효율을 고려한 결로 방지용 예열 온도 예측 모델 개발

주 저자고진영
공동 저자정재원
소속-
AbstractAlthough Korean government tried to enact the law about mandatory pre-heat coil installation in Energy Recovery Ventilator(ERV), the plan was withdrawn due to the concern about excessive energy consumption. Therefore, the other alternative concerning real-time climate difference and effectiveness difference about the pre-heater regulation has been required to prevent the condensation problem. This study suggests a real-time control criterion applying the frost threshold temperature. With the new control measure, not only the energy consumption of pre-heat coil decreased by 61% from the previous suggested method, but also 31% less coil capacity was needed for operation in order to preclude the condensation problem.