header-logo

Exergy analysis on the low flow rate of solution in the atomization-based liquid desiccant system

주 저자Soo-Jin Lee
공동 저자Seong-Yong Cheon, Seheon Kim, Taek-Don Kwon and Jae-Weon Jeong
소속Hanyang University
AbstractThe purpose of this study is to analyse the proposed liquid desiccant absorber with low solution flow rate compared with the conventional packbed-type absorber. The total exergy destruction and exergy efficiency were estimated to assess the system performance. To determine the total exergy destruction and exergy efficiency, it was predicted that the specific thermal and chemical exergy in the inlet and outlet both air and solution side of the absorber. The results indicated that the average total thermal and chemical exergy destruction is 0.054 kW and 0.080 kW in the proposed system while it is 0.292 kW and 0.093 kW in the conventional absorber. The exergy efficiency is 0.573 and 0.114 on average in the proposed and conventional absorber, respectively.
Keyword-
페이지pp. 0~0
논문 파일
게재일시 -
DOI-
학회/저널명CISBAT 2023
년도2023
추가 문구-
등록 일시2025-06-18 19:02:56